SKU 100023- New
- Digital Control Panel
- U.L. Listed
► Micro-processor based design
► Automatic engine starting and
stopping
► Automatic shutdown on fault
condition
► Custom graphical icon LCD
display
► PC configurable via MSWindowsTM
based software
► Provides engine
instrumentation
► Provides generator output
instrumentation
► Provides alarm and status
Information
► Simple selector switch
controlled operation
► Real time diagnostics via MSWindowsTM
► Configurable digital inputs
► Configurable relay outputs
► Configurable timer settings
► Configurable alarm trip points
► Expansion modules for further
enhancement
► External remote start input
► LED & LCD alarm indication
► Adjustable crank
cycle/attempts
► In-built logic for smoke limit
control
DESCRIPTION
The Model 560 is an Automatic Engine
Control Module. The module is used
to automatically start and stop the
engine and indicate operational status
and fault conditions. It will
automatically shut down the engine and
indicate the engine failure by means of a
graphical LCD display and a flashing
LED on the front panel.
Operation of the module is via a threeposition,
rotary switch (key-switch option
available) mounted on the front panel
with STOP, AUTO and MANUAL
positions.
The module features microprocessor
control and provides a comprehensive
list of timers and pre-configured
sequences. This allows complex
specifications to be realised.
Selected operational sequences, timers
and alarms can be altered by the
customer. Configuration changes to the
system are made by using the 808
interface and a PC. This interface also
provides real time diagnostic facilities.
Configurable expansion facilities are
also provided.
The 560 also provides metering and
alarm facilities via the LCD display
which is accessed via the 'display scroll'
push-button. The following
instrumentation displays are available:
► Generator Volts L1-N, L2-N, L3-N
► Generator Volts L1-L2, L2-L3, L3-L1
► Generator Amps L1,L2,L3
► Generator Frequency Hz
► Engine Speed RPM
► Engine Oil Pressure (PSI & Bar)
► Engine Temperature (oC & oF)
► Plant battery Volts
► Engine Hours Run
e.g.
FEATURES
The module accepts the following
digital inputs:
► Emergency Stop Input - N/C DC
positive input
► 5 Fully configurable warning or
shutdown inputs
With the exception of the Emergency
Stop Input, these are configurable to
be either N/C or N/O contacts,
switched to the negative DC. The
five fully configurable auxiliary inputs
can be selected to be indication,
warning or shutdown inputs either
immediate or held off during start-up,
to allow for use as protection
expansion inputs. Alternatively they
may be configured to control extra
functions such as Lamp Test,
Remote Start input and many others.
Engine analogue inputs are
provided for Oil Pressure and Engine
Temperature. These connect to
conventional engine mounted
resistive sender units (such as VDO
or Datcom type) to provide accurate
monitoring and protection facilities.
Alternatively they can be configured
to interface with digital switch type
inputs for Low Oil Pressure and High
Engine Temperature shutdowns.
Description continues overleaf...
DESCRIPTION
CONTINUED
Relay outputs are provided for Fuel
Solenoid, Start Solenoid and three
configurable outputs. The
configurable relay functions can be
selected from a range of different
functions, conditions or alarms. The
relays supply positive plant supply
out. Additional output relays can be
added by means of the 157 Relay
Expansion Module. A total of 11
outputs are available with full
expansion of the 560 Module. This
allows the module system to be
incorporated into existing telemetry
or building management schemes
via volt-free contacts.
Multiple alarm channels are
provided to monitor the following:
► Under/Over Generator Volts
► Under/Over Generator
Frequency
► Under/Overspeed
► Charge Fail
► Emergency Stop
► Low Oil Pressure
► High Engine Temperature
► Fail to Start
► Low/High DC Battery Volts
► Fail to come to rest
► Loss of Speed Sensing Signal
► Generator High Current Warning
along with any configurable input
alarms as selected.
The instrumentation displays are
provided by LCD icon displays for
the various alarms
e.g.
2-colour LED indication is also
provided for alarm present:
Amber steady = Warning
Red flashing = Shutdown
Uncommitted LCD icons allow the
user to configure the module to
provide other status or alarm
indications from either internal states
or from external digital inputs.
The 500 series modules have been
designed for front panel mounting.
The module is fitted into the cut-out
with the fixing clips removed. These
are then fitted from the rear.
Connection is via locking plug and
socket connectors.
► Compliant with BS EN 60950
Low Voltage Directive
► Compliant with BS EN 50081-2
EMC Directive
► Compliant with BS EN 50082-2
EMC Directive
SPECI F ICATION
DC Supply:
8 to 35 V Continuous.
Cranking Dropouts:
Able to survive 0 V for 50 mS,
providing supply was at least 10 V
before dropout and supply recovers
to 5V. This is achieved without the
need for internal batteries.
Max. Operating Current:
390mA at 12 V. 250mA at 24 V.
Max. Standby Current:
220mA at 12 V. 120mA at 24 V.
Alternator Input Range:
15 V(ph-N) to 277 V(ph-N) 3 Phase
4wire AC (+20%)
Alternator Input Frequency:
50 - 60 Hz at rated engine speed
(Minimum: 15V AC Ph-N)
Magnetic Pick-up Voltage Input
Range:
+/- 0.5 V to 70 V Peak
Magnetic Input Frequency: 10,000
Hz (max) at rated engine speed.
Start Relay Output:
16 Amp DC at supply voltage.
Fuel Relay Output:
16 Amp DC at supply voltage.
Auxiliary Relay Outputs:
5 Amp DC at supply voltage.
Dimensions:
192 x 144 x 138
Charge Fail / Excitation Range:
0 V to 35 V
Operating Temperature Range:
-30 to +70°C
TIMERS AND
FUNCTIONS
► Start Delay timer
► Stop Delay timer
► Crank/Crank Rest timers
► Safety On Delay timer
► Warm-up timer
► Cooling timer
► Energise to Stop hold timer
► Pre-heat timer
► Smoke Limiting control timers
► Fail to Stop timer
► Over-speed Overshoot timer
► DC Battery Alarm Delay timers
► LCD Back-lighting for low light
level operation
► Alternator Under/Over Volts
Shutdown
► Alternator Under/Over Freq.
Shutdown
► Under/Over Speed Shutdown
► Low Oil Pressure Shutdown
► High Engine Temp Shutdown
► Low/High Battery Volts
Warning
► Generator High Current
Warning
► Pin compatible with 55x
module
Specifications may vary. Confirm full specs prior to ordering.
Accessories for Control Panels
Voltage Regulators